The loop sounder FI700/WM/MT/SOUR is activated and supplied via the ADM loop with Labor Strauss/700 protocol. Depending on the parameter setup of the fire detection control panel and the system condition, the panel can activate one of three tones. If several sounders are actuated in parallel, they are syn- chronised by the control panel to generate a uniform warning tone
The integrated dual-isolator disconnects the loop at short circuit on the loop line
The sounder is integrated in a red plastic housing and is designed for indoor wall mounting. The sounder base and a special tool for opening the housing are included with the sounder
Tone 1: Slow Whoop tone (NEN 2575; 500 – 1200Hz over 3.5s, 0.5s pause
(Tone 2: DIN tone (DIN 33 404; 1200 – 500Hz over1s
Tone 3: continuous tone 990Hz Low power consumption Adjustable sound leve
Address can be set in the range 1 to 240 by means of Programming Unit FI700/PU
Optional AUTO-addressing when combined with a compatible fire detection control panel
نقد و بررسیها
هنوز بررسیای ثبت نشده است.